Application of Acrel-6000 in the Combat Command Center Project of the Armed Police Heilongjiang Corps

Ankerui Residual Current Electric Fire Monitoring System uses the ARCM residual current electric fire monitoring device or digital residual current transformer to conduct electrical fire monitoring on low-voltage distribution systems in shopping malls, hotels, airports, banks, hospitals, factories and other buildings.
Yang Junjun

Ankerui Electric Co., Ltd. Shanghai Jiading



Abstract: Ankerui residual current electric fire monitoring system uses ARCM residual current type electric fire monitoring device or digital residual current transformer to carry out electrical fire to low-voltage distribution system of shopping malls, hotels, airports, banks, hospitals, factories and other buildings. monitor. This paper introduces the functions and significance of the Acrel-6000 electrical fire monitoring system through the introduction of the electric fire monitoring system project of the Armed Police Heilongjiang Corps Combat Command Center project.



Keywords: electrical fire detector, monitoring equipment, armed police, Ankerui



1 Introduction

The Armed Police Heilongjiang Corps Combat Command Center mainly deals with Heilongjiang Province in peacetime. The Armed Police Force mainly shoulders tasks such as fixed target duty, handling emergencies, and counter-terrorism, and supports national economic construction. In an extraordinary period, the Armed Police Force is a powerful means of suppressing riots, maintaining social stability, and protecting the lives and property of people.



2. System requirements analysis

Detection of leakage current, over current, over temperature and other signals, sound and light signal alarm, accurately report the fault line address, monitor the change of the fault point. Store various fault and operational test signals to display system power status.



3. Reference standard

In recent years, in order to increase the intensity of electrical fire monitoring and prevention, the state has successively formulated or revised a number of relevant standards and regulations to strengthen the prevention of electrical fires. There are:

3.1. GB50045-95 (2005 edition) "Code for Fire Protection Design of High-rise Civil Buildings", which stipulates in Article 9.5.1 that a fire alarm system should be installed in places with high fire risk and dense personnel in high-rise buildings.

3.2. GB50016-2006 "Code for Fire Protection of Building Design", as specified in Article 11.2.7: The following places should be equipped with a residual current action electrical fire monitoring system. These venues include various types of theaters, galleries, warehouses, residential communities, hospitals, shops, schools, and more.

3.3. The relevant provisions of the national standard "Building electrical fire prevention requirements and testing methods" also clearly require that "the residual current action protector that automatically cuts off the power or alarm should be set at the power incoming end".

3.4. The products of the electrical fire monitoring system shall meet: GB14287.1-2005 "Electrical Fire Monitoring Equipment", GB14287.2-2005 "Residual Current Electric Fire Monitoring Detector", GB14287.3-2005 "Measurement Temperature Electric Fire Monitoring and Detection" 》

3.5. The installation and operation of the electrical fire monitoring system shall meet the requirements of GB13955-2005 "Installation and operation of residual current action protection device"

3.6. The power supply of the electrical fire monitoring system shall meet the requirements of GB50052 "Design Specifications for Power Supply and Distribution Systems"

3.7. The design of the electrical fire monitoring system shall meet the requirements of the Design Method of Electrical Fire Monitoring System (Interim Provisions)



4. System composition

The electrical fire monitoring system of the Armed Police Heilongjiang Corps Combat Command Center project consists of electrical fire monitoring equipment, electrical fire detectors and leakage current transformers.

The communication bus of this project is connected to a communication bus. After the bus is connected hand in hand in the power distribution room, it is connected to the wall-mounted background to form the main artery of the electrical fire system. The leakage current transformer in the cabinet is connected to the leakage detector through the current line, and the leakage detector displays the leakage condition in real time. The above describes a set of electrical fire monitoring systems with stable signal and reliable accuracy. The system networking is divided into three layers:

1) Station management

The management of the station control management system for the electrical fire monitoring system is the direct window of human-computer interaction and the uppermost part of the system. Mainly composed of system software and necessary hardware equipment, such as touch screen, UPS power supply and so on. Monitoring system software calculates, analyzes, and China Hardware Business Network Handle and respond to on-site transportation in the form of graphics, digital display, sound, and indicator lights.

Monitoring host: used for data collection, processing, and data forwarding. Provides data interfaces for system management, maintenance, and analysis within and outside the system.

UPS: Ensure the normal power supply of the computer monitoring system, and ensure the normal operation of the station management management equipment when the whole system has power supply problems.

The background monitoring device is set in the self-dimension substation.


2) Network communication layer

Communication medium: The system mainly adopts shielded twisted pair cable, realizes real-time communication between field device and host computer by RS485 interface and MODBUS communication protocol.

3) Field device layer

The field device layer is a data acquisition terminal, mainly for the ARCM200L series of residual electrical fire monitoring detectors.

The system structure topology is shown on the right:



5. Electrical fire equipment

5.1, Acrel-6000 electrical fire monitoring background: China Hardware Business Network

The main technical parameters

power supply:

1 rated working voltage AC220V (-15% ~ +10%)

2 Backup power supply: When the main power supply is under voltage or power failure, maintain the monitoring equipment working time ≥ 4 hours

Working system:

24-hour work schedule

communication method:

RS485 bus communication, Modbus-RTU communication protocol, transmission distance 1km, can extend communication transmission distance through repeater

Monitoring capacity:

1 Monitoring equipment can monitor up to 200 monitoring units (detectors)

2 can be connected with ARCM series monitoring detector

Monitoring alarm items:

1 Residual current fault (leakage): fault unit attribute (part, type)

2 Temperature alarm (over temperature): Fault unit attribute (part, type)

3 Current fault (overcurrent): Fault unit attribute (part, type)

Monitoring alarm response time: ≤30s

Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

Monitoring alarm light display: red LED indicator, red light alarm signal should be maintained until manual reset

Monitoring alarm sound signal: can be manually eliminated, can be started again when there is alarm signal input again

Fault alarm item:

1 The communication cable between the monitoring device and the detector is open or shorted.

2 Monitoring equipment main power supply undervoltage or power failure

3 The cable between the charger that charges the battery and the battery is broken or shorted.

Fault alarm response time: ≤100s

Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

Monitoring alarm light display: yellow LED indicator, yellow light alarm signal should be kept until troubleshooting

Fault alarm sound signal: can be manually eliminated, can be started again when there is an alarm signal input again

The normal operation of the non-faulty loop is not affected during the fault

Control output:

Alarm control output: 1 set of normally open passive contacts, capacity: AC250V 3A or DC30V 3A

Self-test items:

1 Indicator check: alarm, fault, operation, main power, standby power indicator

2 display check

3 audio device inspection

Self-test time ≤60s

record:

1 Record content: record type, time of occurrence, detector number, area, fault description, can store no less than 20,000 records

2 record query: query according to the date, type and other conditions of the record

Operational rating:

1 Daily duty class: real-time status monitoring, event record query

2 Monitoring operation level: real-time status monitoring, event record query, detector remote reset, device self-test

3 System management level: real-time status monitoring, event record query, detector remote reset, device self-test, monitoring device system parameter query, monitoring device module detection, operator addition and deletion

Environmental conditions used:

1 Workplace: Fire control room, manned substation (distribution room), wall on room where someone is on duty

2 Working environment temperature: 0 ° C ~ 40 ° C

3 Working environment relative humidity: 5% ~ 95% RH

4 Altitude: ≤2500m

5.2, ARCM200L series instruments

The ARCM200L residual current type electrical fire monitoring detector is designed for TT and TN systems below 0.4kV. It monitors and manages fire risk parameters such as residual current, wire temperature, over current and over voltage in the distribution circuit. Thereby preventing the occurrence of electrical fires and real-time monitoring of various power parameters, providing accurate data for energy management. The product adopts advanced microcontroller technology, with high integration, small size, convenient installation, intelligent, digital and networked. It is an ideal choice for building electrical fire prevention monitoring and system insulation aging prediction. The product complies with the standard requirements of GB14287.2-2005 "Electrical Fire Monitoring System Part 2: Residual Current Electrical Fire Monitoring Detector".



6. System function

6.1. Monitoring alarm function:

The monitoring equipment can receive the leakage and temperature information of multiple detectors, and emit an audible and visual alarm signal when the alarm occurs. At the same time, the red “alarm” indicator on the device lights up, the display indicates the alarm location and alarm type, and the alarm time is recorded. The sound and light alarm is always maintained. Until the display is reset by pressing the display "Reset" button. The audible alarm signal can also be manually removed using the display "Muffler" button. Hardware Business Network Information Center)http://news.chinawj.com.cn

ISW End Suction Pump

Naipu ISW end suction pumps designed in accordance with ISO2858 standard,are single-stage single-suction horizontal centrifugal pumps featured by integrated simple construction for less space, easy installation, smooth operation with less noise and free of daily maintenance due to the introduction of high quality mechanical seals and closed coupling.

Typical Applications---
Water supply system
Lowering underground water level
Boosting
Gardening and aricultural irrigation

Various kinds of industrial application


ISW End Suction Pump Configuration Drawing

Construction Drawing


Main Part Number At The Drawing

1 Motor
2 Shaft
3 Deflector
4 Mechanical Sea
5 Pressure Monitoring Hole
6 Pump Casing
7 Pressure Release Plug
8 Impeller


ISW END SUCTION PUMP SELECTION CHART

Selection Chart

NP- ISW END SUCTION PUMP PERFORMANCE PARAMETERS

Performance Parameters





ISW End Suction Pump,End Suction Pump,Clear Water Pump,End Suction Water Pump

Shijiazhuang Naipu Pump Co., Ltd. , https://www.naipu-pump.com